Performance:
• Double conversion high frequency online design.
• Using digital control, the system is more stable.
• With input power factor correction (PFC), the input power factor is 0.99.
• The number of battery cells can be set according to user needs: ±16/17/18/19/20 cells.
• With parallel interface, 4 units can be paralleled, and battery packs can be shared in parallel.
• The charging current can be set, and the three-stage charging management of constant voltage, constant current, and floating charge can be automatically switched.
• With LCD and LED dual display, users can intuitively understand the working status and parameters of the UPS.
• With a maintenance bypass switch, which can be maintained when the power is uninterrupted.
• The output load capacity is strong, which can adapt to the unbalanced three-phase load.
• With RS232 communication interface and SNMP (optional) card.
• With emergency shutdown (EPO) button interface, in an emergency, press the EPO button to emergency shutdown.
Specification:
Model | EH9335- 10K | EH9335- 20K | EH9335- 30K | EH9335- 40K |
---|---|---|---|---|
Rated capacity | 10KVA/9KW | 20KVA/18KW | 30KVA/27KW | 40KVA/32KW |
Input | ||||
Input format | Three-phase four-line + ground | |||
Rated input voltage | AC 380V/400V/415V | |||
Voltage range | AC 208V~478V | |||
Frequency range | 45-55Hz at50Hz / 54-66Hz at60Hz (Auto) | |||
Input power factor | ≥0.99 | |||
Input current harmonic | ≤3% (100% Nonlinear load) | |||
Bypass range | Bypass protection voltage upper limit: 220V: +25% (Optional +10%, +15%, +25%)230V: +20% (Optional+ 10%, +15%)240V: +15% (Optional+10%) | |||
Bypass protection voltage lower limit: -45% (Optional -20%-30%) | ||||
Bypass frequency protection range: ±10% | ||||
Outout | ||||
Output format | Three-phase four-line + ground | |||
Rated output voltage | AC 380V / 400V / 415V | |||
Output power factor | 0.8 / 0.9 | |||
Output accuracy | ±1% | |||
Output frequency | Online mode: Follow the utility frequency; Battery Mode: 50/60Hz±0.2% | |||
Output current harmonic | ≤ 2% Linear Load ≤ 5% Nonlinear Load | |||
Battery | ||||
Battery number | 7Ah*40pcs | 7Ah*40pcs | 9Ah*40pcs | 9Ah*40pcs |
Charging Current | 5A max | |||
Protection | ||||
Overload protection | Load 110%, 60min; ≤ 125%, 10min; ≤ 150%, 1min; ≥ 150% Transfer to bypass immediately | |||
Over Temperature Protection | Normal mode: switch to bypass mode; battery mode: shut down output immediately | |||
Emergency shutdown (EPO) | Shut down output immediately | |||
Maintenance bypass | Standard maintenance bypass switch | |||
Other | ||||
Switching time | Utility mode to bypass mode: 0ms; utility mode to battery mode: 0ms | |||
Normal mode (full load) | ≥efficiency 94.5% | |||
Communication interface | RS232,RS485,SNMP Card (optional), electric relay card (optional) | |||
Energy Saving Mode (ECO) | Support | |||
Self-check function | Support | |||
Parallel function | Support up to 4 units in parallel | |||
Executive standard | YD/T1095-2018 | |||
Operating Environment | ||||
Operating temperature | 0~40℃ | |||
Storage temperature | -25~55℃ (batteries: 0~40℃ ) | |||
Operating environment humidity | 0%~95% (no condensation) | |||
Altitude | < 1500m, when above 1500m, when above 1500m, derate according to GB/T 3859.2 | |||
Physical characteristi | ||||
Size (D*W*H) (mm) | 775*335*978 | |||
Net Weight (kg) | 164 | 165 | 166 | 167 |