Performance:
• Double conversion high frequency online design.
• Using digital control, the system is more stable.
• With input power factor correction (PFC), the input power factor is 0.99.
• The number of battery cells can be set according to user needs: ±16/17/18/19/20 cells.
• With parallel interface, 4 units can be paralleled, and battery packs can be shared in parallel.
• The charging current can be set, and the three-stage charging management of constant voltage, constant current, and floating charge can be automatically switched.
• With LCD and LED dual display, users can intuitively understand the working status and parameters of the UPS.
• With a maintenance bypass switch, which can be maintained when the power is uninterrupted.
• The output load capacity is strong, which can adapt to the unbalanced three-phase load.
• With RS232 communication interface and SNMP (optional) card.
• With emergency shutdown (EPO) button interface, in an emergency, press the EPO button to emergency shutdown.
Specification:
Model | EH9335- 10KS | EH9335- 20KS | EH9335- 30KS | EH9335- 40KS | EH9335- 60KS | EH9335- 80KS |
---|---|---|---|---|---|---|
Rated capacity | 10KAVA/9KW | 20KVA/18KW | 30KVA/27KW | 40KVA/32KW | 60KVA/54KW | 80KVA/64KW |
Input | ||||||
Input format | Three-phase four-line + ground | |||||
Rated input voltage | AC 380V/400V/415V | |||||
Voltage range | AC 208V~478V | |||||
Frequency range | 45-55Hz at50Hz / 54-66Hz at60Hz (Auto) | |||||
Input power factor | ≥0.99 | |||||
Input current harmonic | ≤3% (100% Nonlinear load) | |||||
Bypass range | Bypass protection voltage upper limit: 220V: +25% (Optional +10%, +15%, +25%)230V: +20% (Optional+ 10%, +15%)240V: +15% (Optional+10%) | |||||
Bypass protection voltage lower limit: -45% (Optional -20%-30%) | ||||||
Bypass frequency protection range: ±10% | ||||||
Outout | ||||||
Output format | Three-phase four-line + ground | |||||
Rated output voltage | AC 380V / 400V / 415V | |||||
Output power factor | 0.8 / 0.9 | |||||
Output accuracy | ±1% | |||||
Output frequency | Online mode: Follow the utility frequency; Battery Mode: 50/60Hz±0.2% | |||||
Output current harmonic | ≤ 2% Linear Load ≤ 5% Nonlinear Load | |||||
Battery | ||||||
Battery number | Optional: DC±192V/204V/216V/228V/240V (±16/17/18/19/20 pcs) default: DC±192V | |||||
Charging Current | 10A max | 20A max | ||||
Protection | ||||||
Overload protection | Load 110%, 60min; ≤ 125%, 10min; ≤ 150%, 1min; ≥ 150% Transfer to bypass immediately | |||||
Over Temperature Protection | Normal mode: switch to bypass mode; battery mode: shut down output immediately | |||||
Emergency shutdown (EPO) | Shut down output immediately | |||||
Maintenance bypass | Standard maintenance bypass switch | |||||
Other | ||||||
Switching time | Utility mode to bypass mode: 0ms; utility mode to battery mode: 0ms | |||||
Normal mode (full load) | ≥efficiency 94.5% | |||||
Communication interface | RS232,RS485,SNMP Card (optional), electric relay card (optional) | |||||
Energy Saving Mode (ECO) | Support | |||||
Self-check function | Support | |||||
Parallel function | Support up to 4 units in parallel | |||||
Executive standard | YD/T1095-2018 | |||||
Operating Environment | ||||||
Operating temperature | 0~40℃ | |||||
Storage temperature | -25~55℃ (batteries: 0~40℃ ) | |||||
Operating environment humidity | 0%~95% (no condensation) | |||||
Altitude | < 1500m, when above 1500m, when above 1500m, derate according to GB/T 3859.2 | |||||
Physical characteristi | ||||||
Size (D*W*H) (mm) | 690*250*734 | 775*335*978 | ||||
Net Weight (kg) | 50 | 50 | 51 | 52 | 89 | 90 |